=== dc2020-12-0026-guidelines-pages-01.ppm === GUIDELINES ON ENERGY CONSERVING DESIGN OF BUILDINGS - 2020 EDITION Section I. Purpose 1.1 To encourage and promote the energy conserving design of buildings and their services to reduce the use of energy with due regard to the cost effectiveness, building function, and comfort, health, safety, and productivity of the occupants. 1.2 To prescribe guidelines and minimum requirements for the energy conserving design of new buildings and major renovation of existing buildings that fall and are covered under these guidelines and provide methods for determining compliance with the same to make the buildings always energy-efficient. Section II. Definition of Terms 2. As used in these Guidelines, the following shall mean: Air — refers to any of the following: Ambient Air — air surrounding a building; the source of outdoor air brought into a building. Exhaust Air — air removed from a space and discharged to outside the building by means of mechanical or natural ventilation. Indoor Air — air in an enclosed occupiable space. Outdoor Air — ambient air that enters a building through a ventilation system, through intentional openings for natural ventilation, or by infiltration. Return Air — air removed from a space to be recirculated, or exhaust air. Supply Air — air delivered by mechanical or natural ventilation to a space and composed of any combination of outdoor air, recirculated air, or transfer air. Ventilation Air — supply air that is outdoor air plus any recirculated air that has been treated for the purpose of maintaining acceptable Indoor Air Quality. ' Air Conditioning — the process of treating air so as to control simultaneously its temperature, humidity, cleanliness, and distribution to meet the requirements of conditioned space. Air Handling Unit ~ a device used to regulate and circulate air through a duct as part of an air conditioning system. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) — global society founded in 1894, advancing human well-being through sustainable technology for the built environment with focus on building systems, energy efficiency, indoor air quality, refrigeration, and sustainability within the industry. Best Efficiency Point (BEP) — the point along a pump curve where efficiency is the highest. it is the factor to properly assess a pump’s operation. Boiler — a self-contained, low-pressure appliance for supplying steam or hot water. Page 1 of 74 === dc2020-12-0026-guidelines-pages-02.ppm === British Thermal Unit (BTU) — amount of heat energy needed to raise the temperature of one pound of water by one degree Fahrenheit. Building — a permanent structure, whether private or public, enclosed within exterior walls and a roof, and including all attached apparatus, equipment and fixtures, used for any of a wide variety of activities, such as dwelling, entertainment, worship, commercial, industrial, transport, agriculture, public service, education, health care, etc. Certified Energy Conservation Officer (CECO) — a professional who obtains a certification as a CECO after demonstrating high levels of experience, competence, proficiency, and ethical fitness in the energy management profession. The CECO is responsible for the supervision and maintenance of the facilities of Type 1 establishments for the proper management of energy consumption and such other functions deemed necessary for the efficient and judicious utilization of energy. Certified Energy Manager (CEM) ~ a licensed engineer who obtains a certification as a CEM after demonstrating high levels of experience, competence, proficiency, and ethical fitness in the energy management profession, and who is chosen by Type 2 designated establishments to plan, lead, manage, coordinate, monitor and evaluate the implementation of sustainable energy management within their organizations. Coefficient of Performance (COP) — ratio of heating or cooling provided to electrical energy consumed, where higher COPs equate to lower operating costs. Color Rendering — the general expression for the effect of the light source on the color appearance of objects in conscious or subconscious comparison. Color Rendering Index (CRI) — the measure of the degree of color shift, which objects undergo when illuminated by the tight source. Values for common light sources vary from 20 to 99. The higher the number, the better the color rendering or color appearance ({i.e., less color shift or distortion occurs). Cooling Seasonal Performance Factor (CPSF) — quotient of Cooling Seasonal Total Load (CSTL) in (kWh) divided by the Cooling Seasonal Energy Consumption (CSEC) in (kWh). Correlated Color Temperature (CCT) — the absolute temperature (in Kelvin) of the light source. This indicates visual “warmth” or “coolness.” The chromaticity of general lighting lamps falls in the range of 2200 to 7500 K. For interior lighting, the chromaticity values of 4000 K and above are usually described as “cool.” Around 3500 K, light sources have a neutral appearance but, at 3000 K and below, the lighting effect is usually judged as “warm.” Hence, the lower the number, the warmer the light (more red content) and the higher the number, the cooler is the light (more blue content). Covered Buildings — buildings and their systems, which are still to be constructed or under construction, or existing buildings and their systems, which are to undergo or is undergoing expansion and/or modifications, with at least 112.5 kVA of designed total connected electrical loads or has at least 10,000 square meters (m2) Total Gross Floor Area (TGFA). Delta Conversion On-Line Uninterruptible Power Supply (UPS) ~ a new technology introduced to eliminate the drawbacks of the Double Conversion On-Line design and is available in the range of 5kVA to 1 MW. Similar to the Double Conversion On-Line design, the Delta Conversion On-Line UPS always has the inverter supplying the load voltage. However, the additional Delta Converter also contributes power to the inverter output. Under conditions Page 2 of 74 === dc2020-12-0026-guidelines-pages-03.ppm === of AC failure or disturbances, this design exhibits behavior identical to the Double Conversion On-Line. In the Delta Conversion On-Line design, the Delta Converter acts with dual purposes. The first is to control the input power characteristics. This active front end draws power in a sinusoidal manner, by minimizing harmonics reflected onto the utility. This ensures optimal conditions for utility lines and generator systems and reduces heating and system wear in the power distribution system. The second function of the Delta Converter is to charge the battery of the UPS by drawing power and converting it to the appropriate direct current (DC) charging voltage. Design Condition — specified environmental conditions, such as temperature and light intensity, required to be produced and maintained by a system and under which the system shall operate. Designated Establishment — a private or public entity in the commercial, industrial, transport, power, agriculture, public works and other sectors identified by the Department of Energy (DOE) as energy-intensive industries based on their annual energy consumption in the previous year or an equivalent annual index; the amount of consumption as indicated in Republic Act (R.A.) No. 11285 and subject to adjustment by the DOE as it deems necessary Department of Energy (DOE) — the agency created through R.A. No. 7638, otherwise known as the “Department of Energy Act of 1992”, and whose functions were expanded by R.A. No. 9136, otherwise known as the “Electric Power Industry Reform Act of 2001”, R.A. No. 9513, otherwise known as the “Renewable Energy Act of 2008,” and R.A. No. 11285 otherwise k own as the “Energy Efficiency and Conservation Act”. Ductwork — a system of ducts for distribution and extraction of air. Double Conversion On-Line UPS — the most common type of UPS above 10kVA. In the Double Conversion On-Line design, failure of the input AC does not cause activation of the transfer switch, because the input alternating current (AC) is not the primary source, but is rather the backup source. Therefore, during an input AC power failure, on-line operation results in no transfer time. The on-line mode of operation exhibits a transfer time when the power from the primary battery charger battery/inverter power path fails. While a Standby and Line Interactive UPS will exhibit a transfer time when a blackout occurs, a double conversion on-line UPS will exhibit a transfer time when there is a large load step or inrush current. This transfer time is the result of transferring the load from the UPS inverter to the bypass line. Generally, this bypass line is built with dual Silicon Controlled Rectifiers (SCRs), which are very fast, so similar to the Standby and Line Interactive UPS, the transfer time is very brief, usually 4-6 milliseconds. Both the battery charger and the inverter convert the entire load power flow in this design, which causes reduced efficiency and increased heat generation. Electric Discharge Lamp — produces light by the passage of an electric current through a vapor or gas, initiating the discharge to fluoresce or light up. There are two kinds of electric discharge lamp; Low Intensity Discharge (e.g., Fluorescent) and High Intensity Discharge (e.g., Mercury vapor, Metal Halide, High and Low Pressure Sodium). End User — any person or entity requiring the supply and delivery of electricity for its own use. Energy — the capacity to do work. Energy takes a number of forms that may be transformed from one into another such as thermal (heat), mechanical (work), electrical and chemical (BTU or kWh). It refers to all types of energy available commercially, including natural gas (liquid natural gas and liquid oil gas), all heating and cooling fuels (including district heating and district cooling), coal, transport fuels, and renewable energy sources. Page 3 of 74 === dc2020-12-0026-guidelines-pages-04.ppm === Energy Audit — the evaluation of energy consumption and review of current energy cost to determine appropriate intervention measures and efficiency projects in which energy can be judiciously and efficiently used to achieve savings. It may refer to a walk-through audit, a preliminary audit, or a detailed audit. Energy Conservation — the reduction of losses and wastage in various energy stages from energy production to energy consumption through the adoption of appropriate measures that are technologically feasible, economically sound, environmentally friendly, and socially affordable. Energy Efficiency — the way of managing and restraining the growth in energy consumption resulting in the delivery of more services for the same energy input or the same services for less energy input. Energy Efficiency Class (EEC) — the level of the product’s class, which is based on the Cooling Seasonal Performance Factor (CSPF) display on its energy label. Energy Efficiency Classification — the tiers of EEC according to the ranges of CSPF. Energy Efficiency Ratio — the ratio of net cooling capacity (BTU per hour) to total rate of electric input (Watt) under designated operating conditions. Energy Recovery — includes any technique or method of minimizing the input of energy to an overall system by the exchange of energy from one sub-system of the overall system with another. Energy Recovery Ventilation System — a device or combination of devices applied to provide the outdoor air for ventilation, in which energy is transferred between the intake and exhaust air stream. Enthalpy Recovery Wheel — an energy recovery device that transfers outgoing or exhaust air, i.e. temperature and humidity, to the incoming outdoor air. Equivalent Temperature Difference (TDeq) — the temperature difference which results in the total heat flow through a structure as caused by the combined effects of solar radiation and outdoor temperature. Green Energy Option Program (GEOP) — a mechanism to empower end users to choose renewable energy (RE) in meeting their energy requirements. Heating, Ventilating and Air Conditioning (HVAC) — system that helps maintain good indoor air quality through adequate ventilation with filtration and provide thermal comfort. Iuminance (E) — a measure of the amount of light falling on a surface. It is the average illumination of a surface and its unit of measure is Lux (Ix) = Im/m2. Incandescent Lamp — produces light by the passage of an electric current through a filament, which heats it to incandescence (e.g., tungsten and tungsten-halogen). Indoor Environmental Quality (IEQ) — condition inside the building that includes air quality, access to daylight and views, pleasant acoustic conditions, and occupant control over lighting and thermal comfort. Line Interactive UPS — the most common design, where the battery-to-AC power converter Page 4 of 74 === dc2020-12-0026-guidelines-pages-05.ppm === (inverter) is always connected to the output of the UPS. Operating the inverter in reverse during times when the input AC power is normal provides battery charging. When the input power fails, the transfer switch opens and the power flows from the battery to the UPS output. With the inverter always on and connected to the output, this design provides additional filtering and yields reduced switching transients when compared with the Standby UPS topology. In addition, the Line Interactive design usually incorporates a tap-changing transformer. This adds voltage regulation by adjusting transformer taps as the input voltage varies. However, the inverter can also be designed such that its failure will still permit power flow from the AC input to the output, which eliminates the potential of single point failure and effectively provides for two independent power paths. This topology is inherently very efficient which leads to high reliability while at the same time providing superior power protection. Luminaire Efficiency — the ratio between the luminous flux emitted by the luminaire and the luminous flux of the lamp (or lamps) installed in the luminaire. Luminance (L) — the brightness of an illuminated or luminous surface as perceived by the human eye and its unit of measure is cd/m2. Luminous Efficacy (n) — the efficiency with which the electrical power consumed is converted into light and its unit of measure is Im/W. Luminous Flux (#) — the light output of a light source and its unit of measure is Lumen (Im). Luminous Intensity ({) — the measure of light output in a specified direction and the unit of . measure is Candela (cd). Mechanical Ventilation — ventilation provided by mechanically powered equipment such as motor-driven fans and blowers but not by devices such as wind-driven turbine ventilators and mechanically operated windows. Minimum Energy Performance ~ a performance standard which prescribes a minimum level of energy performance for the commercial, industrial and transport sectors, and energy consuming products including appliances, lighting, electrical equipment, machinery and transport vehicles that shall be met or exceeded before they can be offered for sale or used for residential, commercial, transport, and industrial purposes. Natural Ventilation — ventilation provided by thermal, wind, or diffusion effects through doors, window, or other intentional openings in the building. Net Metering — a system, attributed to distributed generation, in which a distribution grid user has a two-way connection to the grid and only charged for his net electricity consumption and is credited for any overall contribution to the electricity grid. Overall Thermal Transfer Coefficient (OTTC) — thermal performance of the building envelope (walls or roof) considering all types of thermal transfer. Pump -~ a rotating machine consisting of an impeller, a pump casing, bearings, bearing frame, shaft and a mechanical seal. The operating principle is to convert mechanical energy to pressure. The pump impeller accelerates a liquid and as the area of the pump casing expands, the velocity of the fluid is converted to pressure. As a result, pressurized fluid exits the pump discharge. Pump is basically an electro-mechanical device. Renewable Energy (RE) Resources — energy resources that do not have an upper limit on the total quantity to be used. Such resources are renewable on a regular basis, and whose Page 5 of 74 === dc2020-12-0026-guidelines-pages-06.ppm === renewal rate is relatively rapid to consider availability over an indefinite period of time. These include, among others, biomass, solar, wind, geothermal, ocean energy, and hydropower conforming with internationally accepted norms and standards on dams, and other emerging renewable energy technologies. Renewable Portfolio Standards (RPS) — a market-based policy that requires electricity suppliers to source an agreed portion of their energy supply from eligible RE resources. Seasonal Energy Efficiency Ratio (SEER) — energy efficiency rating for central air conditioners. Solar Factor — the factor for vertical surfaces, which has been experimentally determined for this geographical zone. Solar Heat Gain Coefficient (SHGC) of Glazing ~ the ratio between the incoming solar radiation behind a glazing and the incoming solar radiation in front of a glazing. Standby-Ferro UPS — was once the dominant form of UPS. This design depends on a special saturating transformer that has three windings (power connections). The primary power path is from AC input, through a transfer switch, through the transformer, and to the output. In the case of a power failure, the transfer switch is opened, and the inverter picks up the output load. In the Standby-Ferro design, the inverter is in the standby mode, and is energized when the input power fails and the transfer switch is opened. The transformer has a special “Ferro- resonant” capability, which provides limited voltage regulation and output waveform “shaping.” Even though it is a standby UPS by design, the Standby-Ferro UPS generates a great deal of heat because the Ferro-resonant transformer is inherently inefficient. The principal reason why Standby-Ferro UPS systems are no longer commonly used is that they can be fundamentally unstable when operating a modern computer power supply load: All large servers and routers use “Power Factor Corrected” power supplies which, when coupled with the Ferro transformer, can give rise to spontaneous and damaging oscillations. Standby On-Line Hybrid — the topology used for many of the UPS under 10kVA which are labeled “online.” The standby DC to DC converter from the battery is switched on when an AC power failure is detected, just like in a standby UPS. The battery charger is also small, as in the standby UPS. Due to capacitors in the DC combiner, the UPS will exhibit no transfer time during an AC power failure. This design is sometimes fitted with an additional transfer switch for bypass during a malfunction or overload. Standby UPS — the most common type used for Personal Computers, the transfer switch is set to choose the filtered AC input as the primary power source (solid line path), and switches to the battery / inverter as the backup source shall the primary source fail. When that happens, the transfer switch shall operate to switch the load over to the battery / inverter backup power source (dashed path). The inverter only starts when the power fails, hence the name “Standby.” Steam System — a steam piping system and controls that work together to supply steam or hot water to heat input devices remote from the Boiler. Supplier — refers to any person or entity authorized by the Energy Regulatory Commission (ERC) to sell, broker, market or aggregate electricity to the end users. Temperature Difference between Exterior and Interior (AT) — the average annual temperature difference between the outside and inside of an air-conditioned building. Page 6 of 74 === dc2020-12-0026-guidelines-pages-07.ppm === Type 1 Designated Establishments — are those with an annual energy consumption of 500,000 kilowatt-hours (kWh) to 4,000,000 kWh for the previous year. Type 2 Designated Establishments — are those with an annual energy consumption of more than 4,000,000 kWh for the previous year. Variable Air Volume System — HVAC System that controls the dry-bulb temperature within a space by varying the volumetric flow of cooled supply air to the space. Variable Frequency Drive (VFD) or Adjustable Frequency Drive (AFD), Variable- Voltage/Variable-Frequency (VVVF) drive, Variable Speed Drive (VSD), AC drive, micro drive or inverter drive — a type of motor drive used in electro-mechanical drive systems to control AC motor speed and torque by varying motor input frequency and voltage. Ventilation — the process of supplying or removing air by natural or mechanical means to or from any space. Such air is not required to have been conditioned. ; Visible Light Transmittance (VLT) — used to determine the amount of light transmitted through the glass. Water Heater — vessel in which water is heated and is withdrawn for use external to the system. Section Ill. Application and Exemption 3.1 Application A. These guidelines are applicable to the design of: 1. New buildings and their systems with at least 112.5 kVA of total connected electrical loads or has at least 10,000 square meters (m2) Total Gross Floor Area (TGFA); and 2. Any expansion and/or modification of existing buildings or systems designed with total connected electrical loads of at least 112.5 kVA or with at least 10,000 square meters (m2) TGFA. B. ~ These guidelines shall not be used to circumvent any applicable safety, health or environmental requirements. 3.2 Exemptions A. Areas with industrial/manufacturing processes. PART | BUILDING ENVELOPE Section IV. Thermal Performance of the Building Envelope 4.1 Scope This section is mandatory for air-conditioned buildings. For non-air-conditioned buildings the requirements defined in this section are not mandatory, but recommendable to improve thermal comfort. The requirements and guidelines in this Page 7 of 74 === dc2020-12-0026-guidelines-pages-08.ppm === 4.2 section cover external walls, roofs, air leakage and reflectance of the roof. The thermal requirements shall apply only to air-conditioned buildings. The building envelope has to be designed to minimize external heat gain, and thereby reduce the cooling load of the air conditioning system. The following describes two methodologies to fulfill building envelope requirements in regard to solar heat load and thermal transmittance: the flexible, but more complex Overall Thermal Transfer Value (OTTV) method, and the easier to apply prescriptive method. OTTV Method A. Approach The solar heat gain through the building envelope constitutes a substantial share of heat load in a building, which shall have to be eventually absorbed by the air-conditioning system at the expense of energy input. To minimize solar heat gain, it is, therefore, the first consideration in the design of an energy- efficient building. The architectural techniques used to achieve the said purpose are too numerous to mention. Siting and orientation of a rectangular building to avoid exposure of its long facades to face east and west, for instance, is a simple means to reduce solar heat gain, if the building site permits. Appropriate choice of building shape to minimize building envelope area and selection of light colors for wall finish to reflect solar radiation are other common-sense design alternatives to lower solar heat input. The OTTV concept takes into consideration the three basic elements of heat gain through the external walls of a building, as follows: * heat conduction through opaque walls; ° heat conduction through glass windows; . solar radiation through the glass windows. ‘These three basic elements of heat input are averaged out over the whole envelope area of the building to give an overall thermal transfer value, or OTTV in short. This concept, in essence, helps to preserve a certain degree of flexibility in building design. Facade For the purpose of energy conservation, the maximum permissible OTTV has been set at 45W/m?. To calculate the OTTV of an external wall, use the basic formula below: OTTV = (Aw x Uw x TDeq) + (Af x Uf x AT) + (Af x SHGC x f x SF) Ao Where: OTTV: overall thermal transfer (W/m?) Aw: opaque wall area (m7) Uw: thermal transmittance of opaque wall (W/m?K) Page 8 of 74 === dc2020-12-0026-guidelines-pages-09.ppm === 1. TDeq: equivalent temperature difference (K), see sub paragraph 1) Af: fenestration area (m2) Uf: thermal transmittance of fenestration (W/m?) AT: temperature difference (K) between exterior and interior, see sub paragraph 2) f: SHGC correction factor f of shading device, see sub paragraph 3) SHGC: solar heat gain coefficient of glazing, see sub paragraph 4) SF: solar factor (W/m?), see subparagraph 5) Ao: gross area of exterior wall (m2) = Avs + Af Equivalent Temperature Difference (TDeq) Equivalent Temperature Difference (TDeq) is the temperature difference which results in the total heat flow through a structure as caused by the combined effects of solar radiation and outdoor temperature. The TDeq across a structure takes into account the types of construction (mass and density), degree of exposure, time of day, location and orientation of the construction and design condition. For the purpose of simplicity in OTTV calculation, the TDeq of different types of construction have been narrowed down to three values according to the densities of the constructions, as given in Table 7. Table 1; Equivalent Temperature Difference for Walls Wall Construction Mass Per Unit Area 9 25 5 kg ra? 126. 195 kegir rer Above 195 kg/m Source: Guidelines on Energy Conserving Design of Buildings, 2007 Temperature Difference between Exterior and Interior AT The temperature difference between exterior and interior AT is the average annual temperature difference between the outside and inside of an air- conditioned building, and is required for calculation of the heat conduction through glazing. In contrary to the equivalent temperature difference TDeq, AT does not consider solar radiation and is therefore with 5 K significantly lower. Correction Factor for the Shading Device The correction factor f is the ratio between the incoming solar radiation behind a shading device and the incoming solar radiation in front of a shading device and is therefore between 0 (opaque) and 1 (no shading). The correction factor can be derived from literature values, manufacturer data, simulation or calculation as shown in Subsection 4 on shading Page 9 of 74 === dc2020-12-0026-guidelines-pages-10.ppm === devices). 4. Solar Heat Gain Coefficient SHGC of Glazing The solar heat gain coefficient is the ratio between the incoming solar radiation behind a glazing and the incoming solar radiation in front of a glazing. The solar heat gain coefficient can be derived from manufacturer data. 5. Solar Factor (SF) ' The Solar Factor for vertical surfaces has been experimentally determined for this geographical zone. From data collected over a period of time for the eight primary orientations, the average Solar Factor for vertical surfaces has been worked out to be 130 W/m*. This figure has to be modified by a correction factor when applied to a particular orientation, and also if the fenestration component is sloped at an angle skyward. For the purpose of the building regulations, any construction having a slope angle of more than 70° with respect to the horizontal shall be treated as a wail. For a given orientation and angie of slope, the Solar Factor is to be calculated from the following formula: SF: 130 x CF (W/m?) Where CF is the correction factor with reference to the orientation of the facade and the pitch angle of the fenestration component and is given in Table 2. Table 2: Solar Correction Factor Wall Slope Angie Notes The correction facters fer iter uricntalaers ened other patty oangles are pour by torte preideel satrt. Source: Guidelines on Energy Conserving Design of Buildings, 2007 As walls at different orientations receive different amounts of solar radiation, it is necessary in general to compute first the OTTVs individual walls, then the OTTV of the whole building envelope. The latter is obtained by taking the weighted average of these values. To calculate for the envelope of the whole building, use the formula below: OTTV = Ao1 X OTTV + + Ag2 X OTTV2 +... +Acx X OTTV, Aoi + Ao2 + ... + Aox The gross area of an exterior wall shall include all opaque wali areas, window areas and door areas, where such surfaces are exposed to outdoor air and enclose an air-conditioned space. The fenestration area Page 10 of 74 === dc2020-12-0026-guidelines-pages-11.ppm === shall include glazing, glazing bars, mullions, jambs, transoms, heads and sills of window construction and shall be measured from the extreme surfaces of the window construction. Where more than one type of material and/or fenestration is used, the respective term or terms shall be expanded into sub-elements, such as: (Aw; x Uw: x TDeq:) + (Aw2 x Uwe x TDeqz), etc. - In the case of a mixed-use building where the residential portion and the commercial portion are distinctly and physically separated from each other, e.g., in the form of a residential tower block and a commercial podium, the OTTVs of the two portions shall be separately computed. Roof For an air-conditioned building, solar heat gain through the roof also constitutes a substantial portion of the cooling load. From on-site solar radiation measurements taken, the intensity of the radiation on a horizontal surface can be as much as 3 times of that on a vertical surface. The purpose of roof insulation is therefore two-folds: to conserve energy in air- conditioned buildings and to promote thermal comfort in non-air-conditioned buildings. In both cases, the building regulations require that the roof shall not have a thermal transmittance or U-value greater than the values tabulated in Table 3. Table 3: Maximum U-value for Roof Se Maximum Thermal TransmitZtance (Wim? K} Air-conditioned Building 50 to 230 Weight Group Non air-conditioned Builcling fight — under 50 mediunt aver 230 heavy Source: Guidelines on Energy Conserving Design of Buildings, 2007 In the case of an air-conditioned building, the concept of OTTV is also applicable to its roof if the latter is provided with skylight. Otherwise, refer to the chapter with the prescriptive method. The OTTV concept for roofs takes into consideration three basic elements of heat gain, as follows: e Heat conduction through opaque roof, e Heat conduction through skylight; e Solar radiation through skylight. The maximum permissible OTTV for roofs is set at 45 W/m?. To calculate the OTTV of a roof, use the same basic OTTV formula for building facade described earlier. Page 11 of 74 === dc2020-12-0026-guidelines-pages-12.ppm === For the purpose of simplicity in OTTV calculation, the TDeq of different types of roof constructions have been standardized in Table 4. Table 4: Equivalent Temperature Difference for Roof > Wall Construction Mass Per Unit Area. - O- SOkgim’? 51. 230 kim’ Ove: 330 kgin’ Source: Guidelines on Energy Conserving Design of Buildings, 2007 Since a roof is more exposed to the sun than a facade, the following solar factor has to be applied for roofs: SF: 320 x CF (Wim?) Where CF is the correction factor with reference'to the orientation of the roof and the pitch angle of the skylight component and is given in Table 5. Table 5: Solar Correction Factor for Roof Orientation Stope Angie noo | 103 103 54 103 | 3 rT ~ ai ~ ” { 4 1S 103 | 105 | 103 | 103 | 103 101 | 703 | ; Fogo | 103 | —-4 +- { i 3 + a eee + nn ee ~-4 i 1Oh | GF TO: 1.08 ior} OSS a4 ogg | i O92 ' —~ + + 4 50" | 0.81 | 089 | 095 | O89 | O83 | O89 | 095 | O89 | ae ce ee San ee ee Cn bree a ee 55" | 077 Osa | 0.91 | O85 | 078 02s | 0% i O84 | 60" | O71 | OBS | OBE | O80 | O73 | OBG | O86 | a7a | : Hy i Hl cn cterew ernest antennae eu fuera nannies tata at nme nn ian ean loeieeenenie manana » cae: Si | 6s" [986 | 074 ; 081 | O78 | 067 | O75 | O81 | O74 | oo [ae ee conn Source: Guidelines on Energy Conserving Design of Buildings, 2007 Note: See Appendix B to D for sample OTTV calculations, thermal! conductivities, K-values, and glass thermai transmittance vaiues. : 4.3 Prescriptive Method A. Solar transmittance of windows Compared with wall assemblies, glazing transfers more heat, and hence, it is ideal to reduce the amount of glazing with respect to the wall in order to reduce internal heat gains. Page 12 of 74 === dc2020-12-0026-guidelines-pages-13.ppm === The requirement of Window to Wail Ratio (WR) needs to be balanced with the amount of daylight coming through the glazed area. Solar Heat Gain Coefficient (SHGC) is used to determine the amount of solar heat admitted through the glass divided by the total solar radiation incident on the glass. Visible light Transmittance (VLT) is used to determine the amount of light transmitted through the glass. WWAR shall be balanced with SHGCaq to maintain flexibility in design. To explain further, the higher the designed building WWR, the lower the required SHGCaq in glass windows shall be and vice-versa. This does not, however, remove the option for building owners to apply windows with low SHGCag for building with low WWR. The size of the opening (with or without glass) shall be in accordance with the National Building Code (NBC), For each WWR value, the SHGCag shall be in accordance with Table 6. The SHGCag requirement in Table 6 can be adjusted if sun breakers are provided in the windows. A sun breaker plays an important role in reducing solar heat gain as it stops solar radiation before it enters the building, and doing so reduces the cooling loads considerably. External shading has the additional positive effect of improving the internal comfort, cutting part of the direct radiation on occupants. This shall be applied only to shaded windows. Table 6: SHGCag for different WWR Maximum SHGCay Source: Prescribed Requirements, IFC Philippine Green Building Code Project, May 2013 SHGCagj limits can be adjusted by multiplying it with the correction factors using the formula: SHGCag = SHGC x f where: SHGC is the adjusted solar heat gain coefficient limit for windows with external shading Page 13 of 74 === dc2020-12-0026-guidelines-pages-14.ppm === 4.4 SHGC is the solar heat gain coefficient of the glazing fis the SHGC correction factor f of the shading device. If there is no shading device, f can be set to 1. SHGC is the solar heat gain coefficient of the glazing and can be derived from the manufacturer data. fis the SHGC correction factor f of the shading device and can be derived by the manufacturer data, simulation, or simplified calculation as described in the next subsection on shading devices. B. Minimum Insulation Values Insulation helps to reduce heat gain in a building, thus improving thermal comfort, acoustic quality, and reducing the load on the air conditioning system. Buildings shall be provided with roof insulation so that the average U-value is maximum 1.4 Wim?Kand the average U-value of the wall is maximum 3.4 W/m?K.Skylights shall have an opening ratio of maximum 5% related to the floor area of the room beneath. Shading Devices and Determination of the Shading Coefficient Shading devices, especially when installed externally, can help improve thermal comfort and significantly reduce energy consumption due to air conditioning in a building. The effectiveness of the shading device is defined by the correction factor f, which is the ratio of solar radiation behind and in front of a shading device. Hence f = 1 if there is a window without shading and f = 0 if the window is opaque. Given the huge variety of shading devices, and hence f factors, take the following into account when determining the f factor: ; 1. manufacturer data 2. simulation 3. calculation One of the most energy- and cost-efficient possibilities for external shading in tropical countries is the fixed overhang and vertical fin. To encourage the provision of sun- shading devices to improve thermal comfort and reduce energy demand, the building regulations make a special provision to relax the requirement pertaining to boundary clearance. Where overhangs, canopies, awnings, or other sun-shading devices are provided, these devices are permitted to project up to a point not less than 1600 mm from the lot boundary instead of the normal requirement of 2300 mm for boundary clearance. To take advantage of this relaxation, the designer shall ensure that only non- combustible materials are used for the construction of the shading devices. It should be noted that the relaxation is only in respect to the projection of shading devices; wall designs shail still comply with the normal boundary clearance requirement. To simplify the determination Process, the f factor for these shading types can be calculated as follows: First, the depth of the overhang or the vertical fin has to be calculated. Second, the height of the window (including the distance between the top part of the frame and the overhang), or the width of the window (including the distance between the frame and’ Page 14 of 74 === dc2020-12-0026-guidelines-pages-15.ppm === 45 the fin), have to be calculated. Figure 1: Schematic Representation of a Window and Related Horizontal Overhang or Vertical Fin DEPTH HEIGHT WIDTH Based on the ratio between the depth of shading and the height/width of window, the correction factor f can be selected from Table 7. Table 7: Correction factor f for external fixed shading Depth/Height ' SHGC Correction Factor f Horizontal Shading Vertical Shading ot , pee nat em tncnennene cen Source: Results of EU-ASEP simulation, 2020 Airtightness of the Building Envelope The infiltration of warm air and moisture and exfiltration of cold air contribute substantially to the heat gain and energy consumption of an air-conditioned building. Also, warm and humid air can cause condensation in the building construction and subsequently lead to mold growth and health problems of the building occupants. As a basic requirement, buildings shall not have unenclosed doorways, entrances, etc.; where heavy traffic of people is anticipated, self-closing doors shall be provided. The concept of an energy-efficient building is based on the assumption that the envelope of the building is completely enclosed to minimize the infiltration of warm air and exfiltration of cool air. Infiltration and exfiltration contribute substantially to the building's heat gain, as the warmer infiltrated air shall be cooled in order to maintain the desired comfort condition. To further minimize the exfiltration of cool air and infiltration of warm air and moisture through leaky windows and doors, effective means of weather-stripping shall also be. incorporated. Additionally, building envelope enclosures such as walls, roofs, and floors on grades shall be non-permeabie to prevent the infiltration of moisture. Preferably, doors and windows shall be designed to meet the following criteria when tested under a pressure differential of 75 Pa: Page 15 of 74 === dc2020-12-0026-guidelines-pages-16.ppm === 4.6 4.7 1. Windows: leakage to limit to 2.77 m*/h per meter of sash crack 2. Swinging revolving or sliding doors: leakage to limit to 61.2 m3/n per meter of door crack 3. Air curtains may be used in very high-volume entrances only when revolving or self-closing sliding doors and vestibules are not appropriate. 4. Entrance vestibules, airlocks, and anterooms shall have at least 3 meters depth/run before the next set of doors. 5. Entrances shall have auto door closers on air locks to keep cold air in and warm air out. Reflectance of the Roof A light-colored building envelope, especially the roof areas which are the most vulnerable, can reduce heat transfer from the outside to the inside of the building by having surfaces with high Solar Reflectance Index (SRI). Roofs shall have one or a combination of the following measures: 1. Roof color with a minimum average SRi of 70 2. More than 70 % of the roof is back ventilated. 3. More than 70 % of the roof is covered by solar thermal and/or PV.. 4. More than 70% is covered by a green roof. Required Design Documentation The following documents shall be required for the building permit application: A. Architectural drawings: e Floor plans with the supporting details and information to satisfy the requirements of this section e Elevations with the supporting details and information to satisfy the requirements of this section e Sectional drawings with the supporting details and information to satisfy the requirements of this section B. Material specifications, e.g. in tender documents or detailed drawings: Windows, skylights: U-value, SHGC value Walls: material type, thickness, k-values Roofs: material type, thickness, k-values Shading: shading length, f-value Insulation specifications supporting wall and roof k-values Roof deck, wall, and floor specification on non-permeable coating C. Proof/Evidence of building envelope compliance OTTV method: OTTV calculation for wall and roof Prescriptive method: calculation of window-to-wall ratio SHGC of glass window to be used Proposed Roof U-value computation Proposed Wall U-vaiue computation Skylight area and roof area computations Page 16 of 74 === dc2020-12-0026-guidelines-pages-17.ppm === 5.1 5.2 e Proposed methods and materials for building airtightness e Proposed SRI of the roof PART Il MECHANICAL SYSTEMS Section V. Air Conditioning and Ventilating System Scope The requirements in this section represent minimum design criteria. Designers shall evaluate other energy conservation measures, which may be applicable to the proposed building or the proposed building renovations. The Philippine Green Building Code (PGBC) applies to all new construction and/or alteration of buildings with a Total Gross Floor Area (TGFA) of 10,000 square meters (m*) or more. In case of conflict between the provisions of the PGBC and these guidelines, the most stringent requirement shall apply. Building owners with buildings with a TGFA of 10,000 m? or more shall be required to submit the building’s annual electricity usage (kWh/year), fuel consumption (liters/year) of generators, and liquefied petroleum gas (LPG) consumption (kg/year). This shall be submitted in the application for the renewal of mechanical systems. Document to be submitted in the report shail be the monthly electrical bills, fuel, and LPG delivery receipts. Load Calculation A. Calculation Procedures Cooling system design loads for the purpose of sizing the system and equipment shall be determined in accordance with the procedures in the latest edition of the ASHRAE Handbook of Fundamentals or other equivalent publications. B. Indoor Design Conditions The indoor conditions in an air-conditioned space shall conform to the following: Design Dry Bulb Temperature 25°C Design Relative Humidity 55% Maximum Dry Bulb Temperature 27°C Minimum Dry Bulb Temperature 23°C Maximum Relative Humidity 60% Minimum Relative Humidity 50% OuRON > Note: Indoor design conditions may differ from those presented above because of special occupancy or process requirement, source control, air contamination, or local regulation. C. Outdoor Design Conditions The outdoor conditions shall be taken as follows for Climate Zone OA: 1. Design Dry Bulb Temperature 35°C 2. Design Wet Bulb Temperature 28°C Notes: See ASHRAE Standard 169-2013 Table A-6 on Philippine Cities Climate Zone in the Appendix Page 17 of 74 === dc2020-12-0026-guidelines-pages-18.ppm === 5.3 D. Ventilation The quality and quantity of air used to ventilate air-conditioned spaces shall always be sufficient and acceptable to human occupation and comply with applicable health and/or air quality requirements. Ventilation requirements shall conform to the design criteria in Table 76. Exception: Outdoor air qualities may exceed those shown in Table 17 because of special occupancy or process requirements, source control air contamination or local regulations. E. Kitchen Ventilation Figures 4 through 9 show the six basic hood styles for Type 1 applications. The style names are not used universally in all standards and codes but are well accepted in the industry. The styles are as follows: 1. Wall-mounted canopy — Used for all types of cooking equipment located against the wall (See Figure 4) 2. Single-island canopy — Used for ail types of cooking equipment in a single- line island configuration (See Figure 5) 3. Double-island canopy — Used for all types of cooking equipment mounted back to back in an island configuration. (See Figure 6) 4. Back shelf — Used for counter-height equipment typically located against the wali, but could be freestanding. (See Figure 7) 5. Eyebrow — Used for direct mounting to oven and some dishwashers. (See Figure 8) 6. Pass-over — Used over counter-height equipment when pass-over configuration (from the cooking side to the serving side) is required. (See Figure 9) System Design and Sizing Air conditioning system and equipment shall be sized as close as possible to the space and system loads calculated in accordance with the subsection on load calculation. The design of the system and the associated equipment and controls shall take into account important factors such as nature of application, type of building construction, indoor and outdoor conditions, internal load patterns, contro! methods for efficient use, and economic factors. A. Engineered systems and equipment shall be properly sized and selected to meet maximum loads and shall have good unloading characteristics to meet the minimum load efficiency. These shall be arranged in multiple units or increments of capacity to meet partial and minimum load requirements without short cycling. Page 18 of 74 === dc2020-12-0026-guidelines-pages-19.ppm === Table 8: Number of Chillers and Water Chiller Types | Table 1.422 Numbor of Critters ae Total Chiller Plant Gapacty “Mumber of Chien j Ht ans, Cee Ee UY iad gas, “Pant miner atthe chats gatest ecctial eechebes a. fargqer vran BOO cans gf suseet osjuatly: Tabie 19.8.2-3 Water Cheiter Types ieedividual Chillar Plant Capenity Elecite Chiller Type | Foss Fisgl ChRter Typa } re Fert Sigdeallert a an brent fre elas feos fA ore. Sartre eget Cyatitbe ate eanpame ghraet fev Source: ASHRAE 90.1-2019 General Notes for Number of Chillers: If the total capacity of the chilled water requirement is over 2,400 TR (8,450 kW), the sizing would be at the discretion of the designer. VFD drive would only be required for units that would be doing peaking loads. Baseload chillers would be soft-starter drive. Table 9: Energy Utilization Index Comparison Energy Utilization indax comparison {RWhISQ eve) Buiiding Use | IFC-PGBI EDGE Philigpine GB ZERO Canto Survey Philippines Cade Min. jdcrwed from 2013 Baseline Compliance ASHRAE 904-2076 tEDGE (Calc} | Office i 345 3 Min. Comphancet [ Residential 65 Condo 1 Hospital S35 Hotcl { Schoo! _ i Retail (Mall} Source: iFC/Green Building Code Survey Table 10: Climate Zone latte 4201.1 Gending Performance Facter QOTs ke a Aron Trine Waiters RAG TTD Sh OF GeO GRA AG Hee DPR asa Oa nese ars Deeg theirs Pe GED GSH St SR TBE aR SA Gd baa GAT AP AAA Sa Ag hoapitat Payee tated rosa ss Re 1 Atha Grete Ol baw 08 Restores Cat 04H GAS GRE Ty TRE Pea SP PS PR OS OO Ah TERR PD OAD PAR Gr ay O47 FOF Tat GIR OFF PAG FAR Ta AT BoA at Macatee s suangen HSS Teds Sn AP RAR Dad SD A AS Fae Oe OAS RAR Tha Rt AT GAT Ab gras CSR CPST COA Pe BS Bd TrGY RAS 1G Ueha OAL At FRA OF Oe rap nar Source: ASHRAE 90.1-2019 Considerations shall be given at the design stage for providing centralized monitoring and control to achieve optimum operations with minimum energy consumption. Page 19 of 74 === dc2020-12-0026-guidelines-pages-20.ppm === 5.4 5.5 Fan System Design Criteria A. General The following design criteria apply to all air conditioning fan systems used for comfort ventilating and/or air conditioning. For the purpose of this section, the energy demand of a fan system is the sum of the demand of all fans required to operate at design conditions to supply air from the cooling source to the conditioned space(s), or exhaust it to the outdoors. Exception: System with a total fan motor power requirement of 5 kW or less. B. Constant Volume Fan Systems For fan systems that provide a constant air volume whenever the fans are operating, ‘the power required by the motor of the combined fan system at design conditions shall not exceed 0.5 W/ m*/h. C. Variable Air Volume (VAV) Fan Systems 1. For fan systems that are able to vary system air volume automatically as a function of load, the power required by the motor of the combined fan system at design conditions shall not exceed 0.5 W/m3/h. 2. Individual VAV fans with motor rated at 5 kW and larger shall include control and devices such as a variable speed drive necessary to make the fan motor operate efficiently even at flow rates of as low as 40% of the rated flow. Electronically commutated (EC) motors shall be used. Pumping System Design Criteria A. General The following design criteria apply to all pumping systems used for comfort air conditioning. For the purpose of this section, the energy demand of a pumping system is the sum of the demand of all pumps required to operate at design conditions to supply fiuid from the cooling source to the conditioned space(s) and return it back to the source. Pumps doing the peaking load shall have VFD drives. Exception: System with total pump motor requirement of 5 kW or less B. Pressure Drop Chilled water and cooling water circuits of air conditioning systems shall be designed at a maximum velocity of 1.2 m/s (3.9 fps) for a 50 mm diameter pipe and pressure drop limit of 39.2 kPa per 100 (4 ft/100 ft) equivalent meter for piping over 50 mm diameter. To minimize erosion for the attainment of the piping system, the water velocities found in Table 20 shall not be exceeded. Page 20 of 74